Acil Durum Aydınlatması Kaçış Yolu Aydınlık Düzeyi Minimum Değerlerinin Deneysel İncelemesi

dc.contributor.advisor Enarun, Dilek tr_TR
dc.contributor.author Jazayerı, Moeın tr_TR
dc.contributor.department Elektrik Mühendisliği tr_TR
dc.contributor.department Electrical Engineering en_US
dc.date 2007 tr_TR
dc.date.accessioned 2015-05-12T12:46:56Z
dc.date.available 2015-05-12T12:46:56Z
dc.description Tez (Yüksek Lisans) -- İstanbul Teknik Üniversitesi, Fen Bilimleri Enstitüsü, 2007 tr_TR
dc.description Thesis (M.Sc.) -- İstanbul Technical University, Institute of Science and Technology, 2007 en_US
dc.description.abstract Bu çalışmada Acil Durum Aydınlatması konusu bir bütün olarak ele alınarak incelenmiştir. Çalışmada acil durum aydınlatması ile ilgili mevcut standartlarda belirlenen aydınlık düzeyi değerleri ve kamaşma limitleri ve acil durum aydınlatma sistemlerinde kullanılan araçlar ve besleme sistemleri incelenmiştir. Tez çalışmasında ayrıca acil durum aydınltması için bazı hesaplama yöntemlerinden örnekler verilerek bu konu ile ilgili daha önce yapılmış olan ve acil durum aydınlatması için gerekli maksimum, minimum ve ortalama aydınlık düzeylerinin bulunması, kamaşma, parıltı faktörlerinin etkileri ve ışık kaynaklarının spektral güç dağılım aralıklarının acil durum aydınlatması üzerindeki etkilerinin bulunmasını amaçlayan çalışmalar incelenerek bu çalışmalardan elde edilen sonuçlar karşılaştırılarak yorumlanmıştır. Tez çalışmasının son bölümünde incelenen örnek çalışmalara benzer acil durum aydınlatma deneyleri yapılımş olup bu deneylerde teorik bilgiler ve standartlarda tavsiye edilen aydınlık düzeylerinin pratik olarak denenmesi ve sonuçta acil durum aydınlatması için insanların bulundukları mekanları güvenli bir şekilde terk edebilmeleri için en uygun aydınlık düzeyinin bulunması ve farklı aydınlık düzeylerinin acil durumlar sırasında insanlar üzerindeki etkilerinin incelenmesi amaçlanmıştır. Farklı aydınlık düzeyleri uygulanarak gerçekleştirilen bu deneylerden elde edilen sonuçlar büyük ölçüde daha önceki çalışmalardan elde edilen sonuçlara benzerlik göstermiş olup deneylerde deneklere uygulanan anketlerden elde edilen sonuçlar incelenmiş ve olumsuz yönlerinin bulunmasına rağmen yine de acil durum aydınlatması için özellikle mekanda bulunan kişilerin mekan ile aşina olmaları halinde 1 lx ortalama aydınlık düzeyinin insanların mekanı terk etmeleri için yeterli ve uygun bir aydınlık düzeyi olduğu sonucuna ulaşılmıştır. tr_TR
dc.description.abstract In this study Emergency Lighting subject is dealt with and examined as a whole. The study considers the illuminance values determined in present standards and glare limits as well as devices used in emergency lighting systems and feeding systems. The treatise equally exemplifies certain calculation methods for emergency lighting and considers the previous works aiming to determine the maximum, minimum and average illuminances necessary for emergency lighting, the effects of factors such as glare and luminance as well as the effects of spectral effects of light sources on emergency lighting and the results of these works have been compared and interpreted. In the last chapter of the treatise, experiments similar to the sample works that are studied and it was aimed to experiment the illuminances recommended in theoretical data and standards and consequently, to find the most suitable lighting levels so that people can leave their places securely and to study the effects of various illuminances on humans in emergency situations. The results obtained from these experiments are mostly similar to those obtained from these experiments and the results obtained from inquiry forms that were filled by volunteers in the experiments and it was found that an average illuminance equaling 1 lx is sufficient and suitable so that people can leave their places for emergency lighting in spite of the unfavorable aspects. en_US
dc.description.degree Yüksek Lisans tr_TR
dc.description.degree M.Sc. en_US
dc.identifier.uri http://hdl.handle.net/11527/1192
dc.publisher Fen Bilimleri Enstitüsü tr_TR
dc.publisher Institute of Science and Technology en_US
dc.rights İTÜ tezleri telif hakkı ile korunmaktadır. Bunlar, bu kaynak üzerinden herhangi bir amaçla görüntülenebilir, ancak yazılı izin alınmadan herhangi bir biçimde yeniden oluşturulması veya dağıtılması yasaklanmıştır. tr_TR
dc.rights İTÜ theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. en_US
dc.subject Aydınlatma tr_TR
dc.subject Acil Durum tr_TR
dc.subject Aydınlık Düzeyi tr_TR
dc.subject Kamaşma tr_TR
dc.subject Parıltı tr_TR
dc.subject Kaçış İşareti tr_TR
dc.subject Kaçış Yolu tr_TR
dc.subject Lighting en_US
dc.subject Emergency en_US
dc.subject Illuminance en_US
dc.subject Glare en_US
dc.subject Luminance en_US
dc.subject Escape Sign en_US
dc.subject Escape Route en_US
dc.title Acil Durum Aydınlatması Kaçış Yolu Aydınlık Düzeyi Minimum Değerlerinin Deneysel İncelemesi tr_TR
dc.title.alternative Emergency Lighting Experimental Analyze Of Minimum Values Of Escape Route Illuminance en_US
dc.type Thesis en_US
dc.type Tez tr_TR
Dosyalar
Orijinal seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.alt
Ad:
4657.pdf
Boyut:
3.65 MB
Format:
Adobe Portable Document Format
Açıklama
Lisanslı seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.placeholder
Ad:
license.txt
Boyut:
3.14 KB
Format:
Plain Text
Açıklama