Konfor Kliması Uygulanan Hacimde Hız Ve Sıcaklık Dağılımının İncelenmesi

dc.contributor.advisor Böke, Erhan tr_TR
dc.contributor.author Eser, Hacı Çağrı tr_TR
dc.contributor.department Isı Akışkan tr_TR
dc.contributor.department Head and Fluids en_US
dc.date 2006 tr_TR
dc.date.accessioned 2015-05-15T07:32:12Z
dc.date.available 2015-05-15T07:32:12Z
dc.description Tez (Yüksek Lisans) -- İstanbul Teknik Üniversitesi, Fen Bilimleri Enstitüsü, 2006 tr_TR
dc.description Thesis (M.Sc.) -- İstanbul Technical University, Institute of Science and Technology, 2006 en_US
dc.description.abstract Bu çalışmada; ofis hacmi için cebri havalandırma durumu incelenmektedir. Sürekli şartlardaki kütlenin korunumu, türbülanslı momentum, türbülanslı enerji, türbülans kinetik enerjisi ve türbülans kinetik enerjisi yayınım oranı denklemleri, tanımlanan sınır şartlarıyla birlikte sayısal akışkanlar dinamiği (SAD) kullanılarak çözülmüştür. Sonlu hacimler yönteminin esas alındığı bir akış analiz programı kullanılmasının yanı sıra kurulan deney düzeneğiyle, kapalı ofis hacmi için oda içersinde oluşan hava hareketleri ve sıcaklık dağılımları incelenmektedir. Deney tesisatı gerçek boyutlarındaki ofis odasının ölçek faktörü olarak 3 alınan bir fiziksel modeli olarak kurulmuştur. Fiziksel benzerlik, eşsıcaklıklı ve eşsıcaklı olmayan oda içersindeki hava hareketlerinin incelenmesinde kullanılan Archimedes (Ar) sayısının eşitliğiyle sağlanmıştır. Ölçümler, sıcak tel anemometreleriyle hava değişim sayısı 5 alınarak elde edilmiştir. Sayısal çözüm olarak, deneyi yapılan modellerin yanı sıra daha farklı üfleme açıklığı konumları ve sıcak üfleme durumu bir CFD programıyla incelenmektedir. Sonuçlar, odaların çeşitli kesitlerinde hız profilleri, hız konturları ve sıcaklık konturları ile gösterilmiş ve insanların konforlu olup olmadığı irdelenmiştir. Ayrıca, beklendiği gibi aynı Ar sayısında oda içersinde benzer hava dağılımları elde edilmiştir. Üfleme açıklığının farklı konumlarının, havalandırılan kapalı hacim içersindeki hava dağılımını ve sıcaklık dağılımını etkilediği gösterilmiştir. tr_TR
dc.description.abstract The forced ventilation of an office space was investigated in this study. Under steady conditions the three-dimensional equations of conservation of mass, momentum, energy, turbulent kinetic energy and its dissipation rate were solved under defined boundary conditions using computational fluid dynamics (CFD). Besides using a flow analysis program, which is based on finite volume method, the air and temperature distribution in a closed office volume was investigated by experiments. The experimental sets up were designed as a physical model by selecting the scale factor as 3. Physical similarity was achieved by the equality of Archimedes number, which was used in determining the isothermal and non-isothermal airflow in closed spaces. Measurements with hot wire anemometers could achieve for the air change rate as 5. The isothermal and non-isothermal flow cases for the physical model were investigated by using a CFD program, by varying the location of the supply air opening. Results were presented in the form of velocity profiles, velocity contours and temperature contours and comfort conditions of the person were investigated. Besides these, the same air distribution patterns were obtained for physical model for the same Archimedes (Ar) number as expectedly. It was shown that the location of supply opening effect the air distribution pattern and temperature distribution in a closed ventilated room. en_US
dc.description.degree Yüksek Lisans tr_TR
dc.description.degree M.Sc. en_US
dc.identifier.uri http://hdl.handle.net/11527/1812
dc.publisher Fen Bilimleri Enstitüsü tr_TR
dc.publisher Institute of Science and Technology en_US
dc.rights İTÜ tezleri telif hakkı ile korunmaktadır. Bunlar, bu kaynak üzerinden herhangi bir amaçla görüntülenebilir, ancak yazılı izin alınmadan herhangi bir biçimde yeniden oluşturulması veya dağıtılması yasaklanmıştır. tr_TR
dc.rights İTÜ theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. en_US
dc.subject Havalandırma tr_TR
dc.subject İklimlendirme tr_TR
dc.subject Havalandırılan oda tr_TR
dc.subject Eşsıcaklıklı ve eşsıcaklıklı olmayan hava akışı tr_TR
dc.subject Fiziksel model tr_TR
dc.subject Hava dağılımı tr_TR
dc.subject CFD programı tr_TR
dc.subject Ventilation en_US
dc.subject Air condition en_US
dc.subject Ventilated room en_US
dc.subject Isothermal and non-isothermal airflow en_US
dc.subject Physical model en_US
dc.subject Air distribution en_US
dc.subject CFD program en_US
dc.title Konfor Kliması Uygulanan Hacimde Hız Ve Sıcaklık Dağılımının İncelenmesi tr_TR
dc.title.alternative Investigation On Velocity And Temperature Distribution Of A Ventilated Room en_US
dc.type Master Thesis en_US