380 Kv Enerji İletim Sisteminde Hat Parafudr Koruması

dc.contributor.advisor Özdemir, Aydoğan tr_TR
dc.contributor.author Öztürk, Hilmi Coşkun tr_TR
dc.contributor.authorID 416821 tr_TR
dc.contributor.department Elektrik Mühendisliği tr_TR
dc.contributor.department Electrical Engineering en_US
dc.date 2011 tr_TR
dc.date.accessioned 2011-10-31 tr_TR
dc.date.accessioned 2015-05-12T12:47:14Z
dc.date.available 2015-05-12T12:47:14Z
dc.date.issued 2011-11-15 tr_TR
dc.description Tez (Yüksek Lisans) -- İstanbul Teknik Üniversitesi, Fen Bilimleri Enstitüsü, 2011 tr_TR
dc.description Thesis (M.Sc.) -- İstanbul Technical University, Institute of Science and Technology, 2011 en_US
dc.description.abstract Bu çalışmada, ATP benzetim yazılımı kullanılarak Türkiye 380 kV’luk elektrik iletim şebekesinin Erzurum-Özlüce enerji iletim hattı modellenmiş ve direklere düşen farklı parametreli yıldırım akımlarının oluşturacağı aşırı gerilimler incelenmiştir. Söz konusu hatta uzunca bir zamandır oluşan geçici açmaların nedenleri ve bunlara karşı alınacak önlemler kapsamında yürütülen tez çalışmasında; direk yapısı, direk topraklama direnci, hattın dalga empedansı, yıldırımın akımının zamanlaması, yıldırım akımının genliği parametre alınarak benzetimler yapılmış ve izolatörlerde oluşacak geçici aşırı gerilimler hesaplanmıştır. Benzetim sonuçlarına göre, yıldırım akımının tepe değeri ve zamanlamasına bağlı olarak, izolatörlerde geri atlama oluşturacak topraklama direnci değerleri belirlenmiştir. Mevcut durumda, farklı parametreler için, izolatörlerde geri atlama oluşturacak gerilimlerin üzerinde bir gerilim oluşmaması için optimum hat parafuduru yerleşimi sağlanmıştır. Elde edilen, benzeri çalışma sonuçlarıyla kıyaslanarak, çalışmanın doğruluğu irdelenmiştir. tr_TR
dc.description.abstract This study presents ATP based simulation of Erzurum- Özlüce transmission line in 380 kV Turkish National Power Transmission system to analyze the overvoltages due to the lightning strokes to the towers. The simulations were performed to determine the transient voltages across the insulator terminals for several different tower configurations, tower grounding resistances, surge impedances of the lines, front times of lightning currents and lightning current magnitudes. Critical grounding resistances ensuring transient voltage magnitudes less than the withstand level of the insulators were determined for several different lightning strokes, optimal surge arresters allocation providing reasonable overvoltages were achived with respect to the probable lightning strokes in Turkey. Simulation results were compared with similar studies to confirm the validation of the allocation. en_US
dc.description.degree Yüksek Lisans tr_TR
dc.description.degree M.Sc. en_US
dc.identifier.uri http://hdl.handle.net/11527/1304
dc.publisher Fen Bilimleri Enstitüsü tr_TR
dc.publisher Institute of Science and Technology en_US
dc.rights İTÜ tezleri telif hakkı ile korunmaktadır. Bunlar, bu kaynak üzerinden herhangi bir amaçla görüntülenebilir, ancak yazılı izin alınmadan herhangi bir biçimde yeniden oluşturulması veya dağıtılması yasaklanmıştır. tr_TR
dc.rights İTÜ theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. en_US
dc.subject Hat Parafudru tr_TR
dc.subject Enerji İletim Hattı tr_TR
dc.subject ATP tr_TR
dc.subject Surge Arrester en_US
dc.subject Power Transmission Line en_US
dc.subject ATP en_US
dc.title 380 Kv Enerji İletim Sisteminde Hat Parafudr Koruması tr_TR
dc.title.alternative Line Surge Arrester Protection Of 380 Kv Power Transmission Line en_US
dc.type Master Thesis en_US
Dosyalar
Orijinal seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.alt
Ad:
12102.pdf
Boyut:
5.66 MB
Format:
Adobe Portable Document Format
Açıklama
Lisanslı seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.placeholder
Ad:
license.txt
Boyut:
3.14 KB
Format:
Plain Text
Açıklama