Havalandırılan Kapalı Bir Hacimde Hava Dağılım Karakteristiklerinin Tayini

dc.contributor.advisor Böke, Erhan tr_TR
dc.contributor.author Yılmaz, Şener tr_TR
dc.contributor.department Enerji tr_TR
dc.contributor.department Energy en_US
dc.date 2005 tr_TR
dc.date.accessioned 2015-10-23T13:31:15Z
dc.date.available 2015-10-23T13:31:15Z
dc.description Tez (Yüksek Lisans) -- İstanbul Teknik Üniversitesi, Fen Bilimleri Enstitüsü, 2005 tr_TR
dc.description Thesis (M.Sc.) -- İstanbul Technical University, Institute of Science and Technology, 2005 en_US
dc.description.abstract Bu çalışmada; ofis hacmi için cebri havalandırma durumu incelenmektedir. Sonlu hacimler yönteminin esas alındığı bir akış analiz programı kullanılmasının yanı sıra kurulan deney düzeneğiyle, kapalı ofis hacmi için oda içersinde oluşan hava hareketleri ve sıcaklık dağılımları incelenmektedir. Deney tesisatı gerçek boyutlarındaki ofis odasının ölçek faktörü olarak 3 alınan bir fiziksel modeli olarak kurulmuştur. Fiziksel benzerlik, eşsıcaklıklı ve eşsıcaklı olmayan oda içersindeki hava hareketlerinin incelenmesinde kullanılan Archimedes (Ar) sayısının eşitliğiyle sağlanmıştır. Hava değişim sayısı 5 alınarak, sıcak tel anemometresiyle yapılan hız ölçümleri çok kısıtlı bir alanda sağlıklı sonuçlar vermiştir. Bu nedenle daha yüksek hızlarda deney yapma gereği duyulduğu için aynı deneyler üfleme kanalı çıkış hızı 4.7 m/s olacak şekilde tekrar yapılmıştır. Sayısal çözüm olarak, deneyi yapılan modellerin yanı sıra daha farklı üfleme açıklığı konumları ve sıcak üfleme durumu bir CFD programıyla incelenmektedir. Birbirinin benzeri olan fiziksel model ve prototipe ait belli çizgiler boyunca elde edilen hız profilleri odada yaşanılan bölgede aynı noktadaki hızların birbiriyle örtüştüğü görülmektedir. Ayrıca, beklendiği gibi aynı Ar sayısında oda içersinde benzer hava dağılımları elde edilmiştir. Üfleme açıklığının farklı konumlarının, havalandırılan kapalı hacim içersindeki hava dağılımını ve sıcaklık dağılımını etkilediği gösterilmiştir. tr_TR
dc.description.abstract The forced ventilation of an office space was investigated in this study. Besides using a flow analysis program, which is based on finite volume method, the air and temperature distribution in a closed office volume was investigated by experiments. The experimental sets up were designed as a physical model by selecting the scale factor as 3. Physical similarity was achieved by the equality of Archimedes number, which was used in determining the isothermal and non-isothermal airflow in closed spaces. Reliable measurements with hot wire anemometer could only be achieved in limited area for the air change rate as 5. Because of the necessity of working with higher velocities, same velocity measurements were carried out with a supply opening for an inlet velocity as 4.7 m/s. The isothermal and non-isothermal flow cases for the physical model were investigated by using a CFD program, by varying the location of the supply air opening. It was seen that the air velocity profiles of physical model and prototype through the occupied zone are strongly the same at same points. Besides these, the same air distribution patterns were obtained for both physical model and prototype for the same Archimedes (Ar) number as expectedly. It was shown that the location of supply opening effect the air distribution pattern and temperature distribution in a closed ventilated room. en_US
dc.description.degree Yüksek Lisans tr_TR
dc.description.degree M.Sc. en_US
dc.identifier.uri http://hdl.handle.net/11527/9824
dc.publisher Fen Bilimleri Enstitüsü tr_TR
dc.publisher Institute of Science and Technology en_US
dc.rights İTÜ tezleri telif hakkı ile korunmaktadır. Bunlar, bu kaynak üzerinden herhangi bir amaçla görüntülenebilir, ancak yazılı izin alınmadan herhangi bir biçimde yeniden oluşturulması veya dağıtılması yasaklanmıştır. tr_TR
dc.rights İTÜ theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. en_US
dc.subject Havalandırılan oda tr_TR
dc.subject Eşsıcaklıklı ve eşsıcaklıklı olmayan hava akışı tr_TR
dc.subject Fiziksel model tr_TR
dc.subject Hava dağılımı tr_TR
dc.subject CFD programı tr_TR
dc.subject Ventilated room en_US
dc.subject Isothermal and non-isothermal airflow en_US
dc.subject Physical model en_US
dc.subject Air distribution en_US
dc.subject CFD program en_US
dc.title Havalandırılan Kapalı Bir Hacimde Hava Dağılım Karakteristiklerinin Tayini tr_TR
dc.title.alternative Determining Air Distribution Characteristics In A Ventilated Room en_US
dc.type Master Thesis en_US
Dosyalar
Orijinal seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.alt
Ad:
2423.pdf
Boyut:
2.32 MB
Format:
Adobe Portable Document Format
Açıklama
Lisanslı seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.placeholder
Ad:
license.txt
Boyut:
3.16 KB
Format:
Plain Text
Açıklama