An experimental study on fire damage of structural steel members in an industrial building

dc.contributor.authorPiroglu, Filiz
dc.contributor.authorBaydogan, Murat
dc.contributor.authorOzakgul, Kadir
dc.contributor.ituauthorBaydoğan, Murat
dc.contributor.ituauthorÖzakgül, Kadir
dc.date.accessioned2026-01-25T11:04:30Z
dc.date.issued2017-10-01
dc.description.abstractAbstract In this paper an experimental study on the fire damage of the unprotected structural steel members is presented after exposure to fire in an industrial fabric established for embellishment of glass wares in 1997. Following the ignited fire flashover occurred, explosions happened, and finally 50,000 m 2 areas were heavily damaged. The structural bearing system of compartments was designed as moment-resistant frames having 11.80 m height. In some halls a space truss roof construction with tubular steel bars which were joining in Mero type assemblies was pin-supported on the columns which were fix on their bottom. Steel columns were made from hot rolled I sections or built-up box sections. Tensile tests were performed on specimens taken from various columns and a tubular space truss member in order to determine post fire mechanical properties. Also, residual factors defined as the ratio of post fire mechanical properties to those at room temperature, and exposed temperatures of the samples were estimated by referring the results of a previous work in the literature. In this approximation, yield strength to ultimate tensile strength ratio of the samples subjected to controlled heating to and cooling from elevated temperatures in the previous work were taken as the reference, and the present results were evaluated based on those results. All the findings obtained from this experimental study were used as a tool in order to get an information about the hazard level which helped for final decision whether removal, reusage or strengthening of the structural steel bearing members might be needed for the compartments of the steel industrial plant exposed to fire hazard.
dc.description.urihttps://doi.org/10.1016/j.engfailanal.2017.06.051
dc.description.urihttps://dx.doi.org/10.1016/j.engfailanal.2017.06.051
dc.identifier.doi10.1016/j.engfailanal.2017.06.051
dc.identifier.endpage351
dc.identifier.issn1350-6307
dc.identifier.openairedoi_dedup___::857e9f73cba11361a380aaf75d5cb592
dc.identifier.orcid0000-0002-3683-8476
dc.identifier.orcid0000-0002-2666-3836
dc.identifier.startpage341
dc.identifier.urihttps://hdl.handle.net/11527/50159
dc.identifier.volume80
dc.language.isoeng
dc.publisherElsevier BV
dc.relation.ispartofEngineering Failure Analysis
dc.rightsCLOSED
dc.sdg.typeGoal 11: Sustainable Cities and Communities
dc.titleAn experimental study on fire damage of structural steel members in an industrial building