Publication: Breakdown characteristics of CO/sub 2/ and N/sub 2/ containing SF/sub 6/ at different gap spacings
Loading...
Date
Authors
Onal, E.
Kalenderli, O.
Mardikyan, K.
Advisor
Department
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE
Type
Abstract
AC breakdown strengths of CO/sub 2/, N/sub 2/, SF/sub 6/ and the mixtures of CO/sub 2/+SF/sub 6/ and N/sub 2/+SF/sub 6/ containing 0.5% and 4% of SF/sub 6/ in a nonuniform field were experimentally studied. The relative gas pressure and the electrode gap spacing were varied within the range of 100-500 kPa and of 5-20 mm respectively. The experimental results have shown that the addition of SF/sub 6/ to CO/sub 2/ and N/sub 2/ causes a significant increase the AC breakdown voltage with respect to CO/sub 2/ and N/sub 2/.
Description
Journal or Series
PowerTech Budapest 99. Abstract Records. (Cat. No.99EX376)