Dağıtılmış Üretim’e Sahip Elektrik Dağıtım Sistemlerinde, Arıza Akımı Sınırlayıcılarının Ve Yerleşim Yerlerinin Etkilerinin İncelenmesi

dc.contributor.advisor Bağrıyanık, Mustafa tr_TR
dc.contributor.author Çakal, Gökhan tr_TR
dc.contributor.authorID 449318 tr_TR
dc.contributor.department Elektrik Mühendisliği tr_TR
dc.contributor.department Electrical Engineering en_US
dc.date 2012 tr_TR
dc.date.accessioned 2012-11-24 tr_TR
dc.date.accessioned 2015-05-12T12:47:17Z
dc.date.available 2015-05-12T12:47:17Z
dc.date.issued 2012-11-26 tr_TR
dc.description Tez (Yüksek Lisans) -- İstanbul Teknik Üniversitesi, Fen Bilimleri Enstitüsü, 2012 tr_TR
dc.description Thesis (M.Sc.) -- İstanbul Technical University, Institute of Science and Technology, 2012 en_US
dc.description.abstract Bu çalışmada arıza akımı sınırlayıcıların elektrik şebekesi üzerindeki etkileri üzerine yoğunlaşılmıştır. Arıza akımı sınırlayıcıların tanımları, özellikleri ve çeşitleri gibi temel kavramlar aktarılmaktadır. Arıza akımı sınırlayıcının sisteme dahil edilmesinin etkileri incelenmiş ve bununla ilgili PSCAD ® bilgisayar programı ile örnek güç sistemleri üzerinde denenmiştir. Örnek test sistemi olarak Fethiye bölgesi’ne ait bir radyal şebeke modeli seçilerek geçici hal analizleri ile akım ve gerilimin değişimi üzerinde incelemeler de bulunulmuştur. Tezde ulaşılmak istenen amaçlardan bir tanesi de dağıtılmış üretim sisteminin etkilerinin arıza akımı sınırlayıcı ile azaltılmasıdır. Arıza akımı sınırlayıcı Fethiye bölgesine ait bir açık halka elektrik şebeke modeli PSCAD ® ile modellenerek geçici hal analizleri yapılmıştır. Tezin asıl amacını oluşturan konu ise, AAS’nin şebeke üzerinde nereye yerleştirileceğidir. Arıza akımı sınırlayıcıların elektrik şebekesine dahil edilirken en uygun yerinin belirlenmesi ekonomik ve etkili bir akım sınırlandırma işlemi için gereklidir. Yanlış bir yere yerleştirilen AAS, arıza akımını azaltmadığı gibi hat kayıplarına ve gerilim değişimlerine neden olmaktadır. Karar verme sürecinde kullanılan ağırlıklı toplam modelinin kriterlerini oluşturan arıza akımındaki azalma, aktif ve reaktif güç kayıpları ile gerilim düşümleri belirlenen ağırlıkları ile en uygun yerin seçiminde karar verici mekanizmayı oluşturmaktadırlar. Aday yerler olarak belirlenen alternatifler içerisinden ağırlığı en yüksek olan aranan çözüm olmaktadır. tr_TR
dc.description.abstract This research mainly focused on the effects of fault current limiters on the power grid. The descriptions of fault current limiters and specifications and variations of these limiters are conveyed in a basic concept. The effects of the inclusion of fault current limiters (FCL) in to the system and the effects were tested on sample power systems with the assistance of PSCAD ®. A radial network in Fethiye was selected. The aim was to analyze transient analysis and the change of the voltage variation. One of the objectives of this thesis is to reduce effects of distributed generation system with the help of fault current limiter. Open-ring electricity network model that belongs to fault current limiter Fethiye was modeled and transient analyses were conducted. The major topic that constitutes the aim of the thesis is where to place FCL in the network. It is substantial to indicate the most appropriate location while including the fault current limiters into the electrical network in terms of economic reasons and to succeed in the process of efficient current limitation. FCL placed in the wrong place both does not decrease the fault current and causes the loss of line and changes of voltages. The decrease in the level of fault current that generates the weighted sum model, the loss of active and reactive power and voltage drops, together with their weight, constitute a decision-making mechanism in the process of selecting the most appropriate place. The highest weight within the alternative places determined as candidate. en_US
dc.description.degree Yüksek Lisans tr_TR
dc.description.degree M.Sc. en_US
dc.identifier.uri http://hdl.handle.net/11527/1321
dc.publisher Fen Bilimleri Enstitüsü tr_TR
dc.publisher Institute of Science and Technology en_US
dc.rights İTÜ tezleri telif hakkı ile korunmaktadır. Bunlar, bu kaynak üzerinden herhangi bir amaçla görüntülenebilir, ancak yazılı izin alınmadan herhangi bir biçimde yeniden oluşturulması veya dağıtılması yasaklanmıştır. tr_TR
dc.rights İTÜ theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. en_US
dc.subject Arıza akımı sınırlayıcı tr_TR
dc.subject Dağıtılmış üretim tr_TR
dc.subject En uygun yer seçimi tr_TR
dc.subject Fault current limiter en_US
dc.subject Distributed Generation en_US
dc.subject Optimum Location Selection en_US
dc.title Dağıtılmış Üretim’e Sahip Elektrik Dağıtım Sistemlerinde, Arıza Akımı Sınırlayıcılarının Ve Yerleşim Yerlerinin Etkilerinin İncelenmesi tr_TR
dc.title.alternative A Study Of The Effects Of Fault Current Limiters And Their Location On Power Distribution System With Distributed Generation en_US
dc.type Thesis en_US
dc.type Tez tr_TR
Dosyalar
Orijinal seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.alt
Ad:
13107.pdf
Boyut:
1.83 MB
Format:
Adobe Portable Document Format
Açıklama
Lisanslı seri
Şimdi gösteriliyor 1 - 1 / 1
thumbnail.default.placeholder
Ad:
license.txt
Boyut:
3.14 KB
Format:
Plain Text
Açıklama