A parametric CFD study of computer room air handling bypass in air-cooled data centers

Loading...
Thumbnail Image

Institution Authors

Item type:Person,
Erden, Hamza Salih
Docent

Advisor

Department

Journal Title

Journal ISSN

Volume Title

Publisher

Elsevier BV

Research Projects

Organizational Units

Journal Issue

Abstract

Abstract Computer room air handling (CRAH) bypass (BP) method is an application that reduces the total fan power in air-cooled data centers by lowering CRAH fan speed. BP fans supply the complementary fraction of server airflow from warmer room air through lower-resistance floor openings into the plenum. Hence, chillers need to operate at lower temperatures less efficiently, which poses an optimization problem. The reduced-order modeling tools in the literature adequately predict fan power. However, they assume well-mixed temperature at rack inlets to deal with this optimization problem and fail to quantify the impact of ignoring temperature non-uniformities. This study includes an experimental verification of computational fluid dynamics (CFD) modeling for CRAH BP method in predicting temperatures in a data center test-cell. The subsequent parametric study uses both CFD and reduced-order modeling tools on a more representative quadrant of a large data center to investigate induced and forced CRAH BP in both enclosed and open aisle configurations as well as comparing various plenum heights, IT load and server airflow rate. Results indicate where reduced-order modeling tools perform reasonably well and where the need for CFD emerges and identify various favorable data center designs and operating conditions for CRAH BP method.

Description

Journal or Series

Applied Thermal Engineering

ISSN

1359-4311

ISBN

Rights

OPEN

Keywords

Citation

Collections

Endorsement

Review

Supplemented By

Referenced By

Related Patent

Related Goal

2
Görüntülenme
0
İndirme
Altmetric
Dimensions
PlumX Metrikleri
BIP! Indicators
Google Scholar
Scholar'da Ara ↗