<link rel="stylesheet" href="styles.cf390c6bfbe7555f.css">

Publication:
Trihalomethane (THM) reduction in Istanbul water treatment plants

dc.contributor.authorEroğlu, V.
dc.contributor.authorSaatçı, A.M.
dc.date.accessioned2026-01-25T23:41:12Z
dc.date.issued2001-03-01
dc.description.abstractThis paper describes trihalomethane reduction in an Istanbul drinking water plant. The total THM levels (TTHM) could be controlled by decreasing the post-chlorination doses. After the commencement of the pre-ozonation process, pre-chlorination was terminated and a sudden drop of THM values in the effluent of the plant was observed. A predictive model that gives a good fit to the observed TTHM levels during the 7 months operation of the plant with and without the pre-ozonation process was presented.
dc.description.urihttps://doi.org/10.2166/ws.2001.0035
dc.description.urihttps://dx.doi.org/10.2166/ws.2001.0035
dc.identifier.doi10.2166/ws.2001.0035
dc.identifier.eissn1607-0798
dc.identifier.endpage181
dc.identifier.issn1606-9749
dc.identifier.openairedoi_dedup___::a40dcf40c2429b7933bfb241b975c4cd
dc.identifier.startpage175
dc.identifier.urihttps://hdl.handle.net/11527/52969
dc.identifier.volume1
dc.language.isoeng
dc.publisherIWA Publishing
dc.relation.ispartofWater Supply
dc.rightsOPEN
dc.sdg.typeGoal 6: Clean Water and Sanitation
dc.titleTrihalomethane (THM) reduction in Istanbul water treatment plants
dc.typeArticle
dspace.entity.typePublication

Files

Collections