Publication: Innovative volt/var control method tap staggering analysis and effects on the adaptive protection system in networks with renewable energy sources
Loading...
Files
Date
Authors
Advisor
Department
Journal Title
Journal ISSN
Volume Title
Publisher
Graduate School
Type
Abstract
The increasing presence of distributed generation sources of renewable energy on current networks poses many technical difficulties, which comprises issues associated with voltage and protection system malfunctions due to bidirectional power flow and altered grid dynamics. One of these challenges which is overvoltage problem has the potential to damage network equipment and induces quality related power issues. To resolve these issues, one of the innovative Volt/VAr control methods such as Tap Staggering could potentially be used. The Tap Staggering method uses the circulating current obtained by deliberately creating a tap level difference between parallel transformers to ensure reactive power absorbing from the grid. This method is applied to identical parallel transformers to achieve reactive power absorption, thereby reducing the voltage level in the grid. However, absorbing reactive power by the distribution substation using the Tap Staggering method poses a significant threat to protection system of te network, especially for the DOC with Load Blinder protection schema. Under normal load conditions, this situation may result in faults or undesired tripping. Therefore, this study investigates the impacts of the Tap Staggering method on the grid and adaptive protection system. Grid models are created based on a specific section of a real network, using changing grid models depending on 24 hour demand/generation profile of the loads and the wind turbines. In addition to these scenarios, Tap Staggering is applied with 5 different step sets, resulting in a total of 120 different scenarios. To analyze these scenarios, Tap Staggering Macro and Adaptive Protection Macro are developed which are contain automated network scenario change based on the hourly demand/generation levels, evaluation of the defined measurements and adaptation of the protection parameters based on the equations. The study results indicate that the application of the Tap Staggering method solves the overvoltage problems in the transmission network with an effective way through absorption of reactive power. In spite of the fact that there is an increase in the parallel transformers' active power loss as the tap difference between parallel transformers is widened, the evaluation based on the transformer efficiencies shows that power loss remains within standards. On the other hand, it is concluded that the Tap Staggering method influences the DOC with Load Blinder protection schema and restricts the transmission of power generated from wind turbines on the distribution grid to the transmission grid and beyond. Application of the Tap Staggering method influences minimum and maximum short-circuit fault currents and active-reactive power values in the grid and reverse power flow current and power flow angle measured on the relay causing changes in DOC with Load Blinder protection schema parameters (i.e., I>$_D_O_C$ pickup, R$_L_B$ and $\alpha$). For that reason, adaptation of the DOC with Load Blinder protection schema parameters is required for the entire studies. After adaptation of the parameters, the protection system performs reliably, and the power generation based on wind resource in the distribution grid is efficiently transmitted to the transmission grid and beyond without constraints.
Description
Thesis (M.Sc.) -- İstanbul Technical University, Graduate School, 2024
Journal or Series
ISSN
ISBN
Rights
Keywords
renewable energy, yenilenebilir enerji
Citation
Collections
Endorsement
Review
Supplemented By
Referenced By
Google Scholar
Scholar'da Ara ↗ Bu yayında DOI yok — Altmetric/Dimensions/PlumX/BIP! rozetleri DOI gerektirir.